| Features |
- T/C, RTD, Linear Input selection.
- Open Loop. Close Loop Control selection.
- Auto/manual Bumpless Transfer.
- LED Bar indicator to show valve position.
- Standby and Latch mode can be combined with 6 different alarm function.
- 2 alarm output.
- Universal Power Supply : 90-264V AC, 50/60Hz. DC / AC 24V is also available for option.
- Fuzzy enhanced PID control.
|
| Optional |
- Open Loop. Close Loop Control selection.
- Auto/manual Bumpless Transfer.
|
| Specifications |
| Input |
Thermocouple: J. K. T. E. B. R. S. N.C |
| RTD: DIN PT-100; JIS PT-100 |
| Linear: 4~20mA; 0~50mV; 1~5V; 0~10V… |
| Accuracy |
T/C±1°C; RTD±0.2°C; Linear±3µV |
| Sampling Time |
0.25 sec. |
| Control |
Proportional band: 0.0~300.0% F.S |
| Integral time: 0~3600 sec. |
| Derivative time : 0~900 sec. |
| Hysteresis: 0.0~200.0 or 0.0~2000 |
| Feed back potentiometer of valve:≧250Ω |
| Valve Travel Time |
0~1000 sec |
| Output |
OPEN : Relay contact output: 5A/ 240 VAC (Resistive load) |
| CLOSE:Relay contact output: 10A/ 240 VAC (Resistive load) |
| General |
Rated Voltage: AC 90~264VAC 50 / 60HZ; DC 24V |
| Ambient Temperature: 0~50°C |
| Ambient Humidity: 0~90 % |
| Consumption: Less than 5VA |
| Input |
| Type |
TEMPERATURE RANGE ( °C ) |
TEMPERATURE RANGE ( °F ) |
| J |
-50°C ~ 1000 °C |
-58°F~ 1832°F |
| K |
-50°C ~ 1370°C |
-58°F~ 2498°F |
| T |
-270°C ~ 400°C |
-454°F~ 752°F |
| E |
-50°C ~ 750°C |
-58°F~ 1382°F |
| B |
0°C ~ 1800°C |
32°F~ 3272°F |
| R |
0°C ~ 1750°C |
32°F~ 3182°F |
| S |
0°C ~ 1750°C |
32°F~ 3182°F |
| N |
-50°C ~ 1300°C |
-58°F~ 2372°F |
| C |
-50°C ~ 1800°C |
-58°F~ 3272°F |
| DPT |
-200°C ~ 850°C |
-328°F~ 1652°F |
| JPT |
-200°C ~ 650°C |
-328°F~ 1202°F |
| LINE |
-1999 ~ 9999 |
| Alarm Function |
| PV High Alarm |
PV Low Alarm |
| Deviation High Alarm |
Deviation Low Alarm |
| Band Low Alarm |
Band High Alarm |
|
 |
| Dimension |
 |
| Wiring Diagram |
 |
| Ordering Information |
 |
|
| ^ TOP |