> PID Controllers > VT Series
 
VT 26 Fuzzy Enchanced VT9621 Fuzzy Enhanced Dual Channel PID Controller
   

VT26 Fuzzy Enhanced

Download CatalogCatalog Download ManualManual Download RS-485RS-485
   
Features
  • T/C, RTD, Linear Input selection.
  • Fuzzy enhanced PID Control.
  • Auto / Manual Bumpless Transfer.
  • Two alarm output.
  • Standby and Latch mode can be combined with 8 different alarm functions.
  • Ramp to setpoint and soak functions.
  • Soft- start function.
  • Universal power supply : 90-264V AC, 50/60Hz.

Optional
  • Output 2 for cooling control.
  • PV or SV retransmission.
  • Master & Slaver transmission.
  • RS-485 communication. (MODBUS RTU)
  • Power supply : DC 24V

Specifications
Input Thermocouple: J. K. T. E. B. R. S. N.C
RTD: DIN PT-100; JIS PT-100
Linear: 4~20mA; 0~50mV; 1~5V; 0~10V…
Accuracy T/C±1°C; RTD±0.2°C; Linear±3µV
Sampling Time 0.25 sec.
Control Proportional band: 0.0~300.0% F.S
Integral time: 0~3600 sec.
Derivative time : 0~900 sec.
Hysteresis: 0.0~200.0 or 0.0~2000
Cycle Time: 0~100 sec.
Cycle Time (0~100) Relay 15 sec.
Pulsed voltage to drive SSR: 1sec.
Continuous current (Voltage): 0 sec.
Output Relay contact output: 10A/ 240 VAC (Resistive load)
Pulsed Voltage Output to Drive SSR: DC 0/24V
(Resistive 250 min.)
Current Output: 4~20mA; (Resistive 600 max.)
Continuous Voltage Output: 0~50mV; 1~5V; 0~10V.....
(Resistive 600 min.)
General Rated Voltage: AC 90~264VAC 50 / 60HZ; DC 24V
Ambient Temperature: 0~50°C
Ambient Humidity: 0~90 %
Consumption: Less than 5VA




Dimension

Wiring

Order Information

^ TOP

VT9621 Fuzzy Enhanced Dual Channel PID Controller

Download CatalogCatalog Download ManualManual Download RS-485RS-485
   
Features
  • Independent duel input channel.
  • T/C, RTD, Linear input selection.
  • Fuzzy enhanced PID control.
  • Auto / Manual Bumpless Transfer.
  • Two alarm output.
  • Ramp function.
  • Soft- start function.
  • Auxiliary DC24V power supply to drive transmitter.
  • Universal power supply : 90-264V AC, 50/60Hz.

Optional
  • Output 2 for cooling control.
  • Process value or setpoint value Retransmission.
  • 4-20mA remote setpoint input.(SP-2)
  • Master & Slaver transmission
  • RS-485 communication (MODBUS RTU)
  • Power supply : DC/AC 24V

Specifications
Input Thermocouple: J. K. T. E. B. R. S. N.C
RTD: DIN PT-100; JIS PT-100
Linear: 4~20mA; 0~50mV; 1~5V; 0~10V…
Accuracy T/C±1°C; RTD±0.2°C; Linear±3µV
Sampling Time 0.25 sec.
Control Proportional band: 0.0~300.0% F.S
Integral time: 0~3600 sec.
Derivative time: 0~900 sec.
Hysteresis: 0.0~200.0 or 0.0~2000
Cycle Time: 0~100 sec.
Output Cycle Time Relay 15 sec.
Pulsed voltage to drive SSR: 1sec.
Continuous current (Voltage): 0 sec.
Output Relay contact output: 10A/ 240 VAC (Resistive load)
Pulsed Voltage Output to Drive SSR: DC 0/24V
(Resistive 250 min.)
Current Output: 4~20mA; (Resistive 600 max.)
Continuous Voltage Output: 0~50mV; 1~5V; 0~10V.....
(Resistive 600 Ωmin.)
General Rated Voltage: AC 90~264VAC 50 / 60HZ; DC 24V
Ambient Temperature: 0~50°C
Ambient Humidity: 0~90 %
Consumption: Less than 5VA

Input
Type TEMPERATURE RANGE ( °C ) TEMPERATURE RANGE ( °F )
J -50°C ~ 1000 °C -58°F~ 1832°F
K -50°C ~ 1370°C -58°F~ 2498°F
T -270°C ~ 400°C -454°F~ 752°F
E -50°C ~ 750°C -58°F~ 1382°F
B 0°C ~ 1800°C 32°F~ 3272°F
R 0°C ~ 1750°C 32°F~ 3182°F
S 0°C ~ 1750°C 32°F~ 3182°F
N -50°C ~ 1300°C -58°F~ 2372°F
C -50°C ~ 1800°C -58°F~ 3272°F
DPT -200°C ~ 850°C -328°F~ 1652°F
JPT -200°C ~ 650°C -328°F~ 1202°F
LINE -1999 ~ 9999

Dimension

Wiring

Order Information
^ TOP